Model Number (Final ordering #/Part No to be defined)
Voltage (V)
Current (A)
Power (W)
RFQ
GTM43007-A3005-FW*
5
6
30
GTM43007-A3007-1.0-FW*
6
5
30
GTM43007-A3007-FW*
7
4.28
29.96
GTM43007-A4509-1.5-FW*
7.5
6
45
GTM43007-A3809-1.5-FW*
7.5
5
37.5
GTM43007-A4509-FW*
9
5
45
GTM43007-A4512-2.0-FW*
10
4.5
45
GTM43007-A6012-FW*
12
5
60
GTM43007-A4512-FW*
12
3.75
45
GTM43007-A6015-1.2-FW*
13.8
4.347
59.99
GTM43007-A3515-FW*
15
2.333
35
GTM43007-A6015-FW*
15
4
60
GTM43007-A6015-FW*
15
4
60
GTM43007-A3517-FW*
17
2.060
35.02
GTM43007-A6018-1.0-FW*
17
3.53
60.01
GTM43007-A6018-FW*
18
3.333
59.99
GTM43007-A1018-FW*
18
0.555
9.99
GTM43007-A6024-5.0-FW*
19
3.15
59.85
TR9WH1000T00-IMR6B*
GTM96180-1830-12.0-T2A, ICT / ITE / Medical Power Supply/Class 2/Household Power Supply, Efficiency Level: USA DOE Level VI / Eco-design Directive 2009/125/EC, (EU) 2019/1782, Case Color/Style: GlobTek Black, Desktop/External, Regulated Switchmode AC-DC Power Supply AC Adaptor, Input Rating: 100-240V~, 50-60 Hz, IEC 60320/C18 , Output Rating: 18W, 18.0V@1.0A, Output Configuration: 1500 mm, 18/2 Cond, Round Black, T-plug system (includes 5.5x2.5, 5.5x2.1, 3.5x1.3mm plugs in each kit), Ferrite: None, GlobTek Black, GT Cord # C3775, Pin Out: Polarity Configuration T00 All plugs are Medical Grade, Locking, Polarized once installed, and single use only. Product demonstration link: https://en.globtek.com/news/t00-changeable-output-plug-system-for-power-supplies MOLDED CONNECTORS AVAILABLE, Blades/Input Cord: (Order Separately), Approvals: cETLus 60601-1 3rd; CB 61558-2-16; 230V CoC Tier 2; Fuse 60335; CB 60601-1; CB 60950; CB 60335; CB 62368; CCC; CE; CE; ETL; PSE; PSE; PSE; China RoHS; Level VI; LPS 60950; RoHS; Ukraine; VCCI; WEEE; FCC; CAN ICES-3; S-Mark 60950; Double Insulation; cETLusUL1310; Fuse 60335; IP42; IRAM; EAC; UKCA; LPS 62368; NrCAN (9V only); UL 1310; ETL 62368; Conforms to 62368-1; Morocco; S-Mark 62368; IRAM; RCM; to , GT Cable #: / Conductors, mm OD, , Deg.C,
GTM43007-A6024-4.0-FW*
20
3
60
GTM43007-A6024-FW*
24
2.5
60
GTM43007-A6036-8.4-FW*
27.6
2.18
60.17
GTM43007-A6036-6.0-FW*
30
2
60
GTM43007-A5136-2.5-FW*
33.5
1.5
50.25
GTM43007-A6036-2.5-FW*
33.5
1.79
59.97
GTM43007-A6036-FW*
36
1.66
59.76
GTM43007-A6048-8.0-FW*
40
1.5
60
GTM43007-A6048-FW*
48
1.25
60
* (Final ordering #/Part No to be defined)
Specifications
A) ELECTRICAL SPECIFICATIONS: 01. Input Voltage: Specified 90-264 Vac, Nameplate rated: 100-240Vac 02. Input Frequency: Specified 47-63 Hz, Nameplate rated 50-60Hz 03. Output Regulation: +/- 3% measured at the output connector 04. Line Voltage Regulation: +/- 0.5% maximum measured at full load 05. Output Ripple (Vp-p): +/- 1% of output voltage, Vp-p, max 06. Turn-ON/OFF: 5% maximum,1 mS typical recovery time for 25% step load 07. Turn-ON Delay: 1 Sec max 08. Hold-Up Time:10 mS typical @ nominal input voltage and full load 09. Inrush Current: 80A maximum @ 115 Vac input, 160A maximum @ 230 Vac input 10. Switching Frequency: 65 KHz typical 11. Efficiency: 87% @115Vac, 89% @ 230Vac typical at full load 12. No Load Power: < 300mW @ 230Vac
B) PROTECTION 01. Overvoltage Protection: 110% to 130% of nominal output voltage, and less than 60Vdc 02. Short Circuit/Over-load: momentary short circuit protected, output will auto recover upon removal of short
C) SAFETY 01. Dielectric Withstand Voltage: 4000Vac / 5656Vdc from primary to secondary 02. Earth Leakage Current: Does not exceed 300uA in NORMAL CONDITION and 1000uA in SINGLE FAULT CONDITION 03. Output Leakage Current: Does not exceed 75uA NC(Normal condition) 300uA SFC(single fault condition) 05. Earth continuity test:<0.1 Ohm, Class I Only 06. Mode of operation: Continuous 07. Means of Protection: 2 x MOPP 08. Compliant Standards: See listings at end of this drawing for specifics
D) EMC EN 60601-1-2, 4th edition Emissions, per EN 55032, EN 61000-6-3, EN 61000-6-4 Conducted Emissions: Class B, FCC Part 15, Class B Radiated Emissions: Class B, FCC Part 15, Class B Line Frequency Harmonics EN61000-3-2, Class A Voltage Fluctuations/Flicker EN61000-3-3
Immunity, per EN 55024, EN 61000-6-1, EN 61000-6-2 Static Discharge Immunity EN61000-4-2, 10kV Contact Discharge, 20kV air discharge Radiated RF Immunity EN61000-4-3, 10V/m 80-1000MHz, 3V/m 1-2.7GHz, 80% 1KHz AM. EFT/Burst Immunity EN61000-4-4, 4kV/100kHz. Line Surge Immunity EN61000-4-5, 2kV differential, 4kV common-mode Conducted RF Immunity EN61000-4-6, 3Vrms, 80% 1KHz AM Power Frequency Magnetic Field Immunity EN61000-4-8, 3A/m Voltage Dip Immunity EN61000-4-11, Criteria
E) OTHER 01. MTBF: 1,000,000 Hours @ 45°C ambient temperature, Full Load 02. Operating Temperature: -10°C to 45°C ambient temperature 03. Humidity: 0% to 95% relative humidity 04. Storage Temperature: -30°C to 80°C 05. Cooling: Convection 06: Elevation: 5000M 07. ROHS: Complies with EU 2011/65/EU amended by EU 2015/863 and China SJ/T 11363-2006
F) MECHANICAL FORMAT 01. Type: Open Frame 02. Size: A suffix version, (2”x3”), 76.2 x 50.8 x 30.5 mm 03. Size: B suffix version, (2”x4”), 101.6 x 50.8 x 30.5 mm 04. Size: C suffix version, (3”x5”), 127.0 x 76.2 x 30.5 mm
G) SPECIAL OPTIONS 01. Custom Label Markings 02. Short term Output Surge Capability 03. Reduced Leakage Current versions 04. Tightened output voltage tolerance 05. Reduced output ripple level 06. High Rel PCB laminate with Plated through Holes for IPC610 Class 2 Compliance 07. Low Temperature operation, down to -40°C 08. Quasi Constant Current Output, for Lead-Acid Battery Charger Applications 09. Special Input or Output Connectors 10. Over-Temperature Protection, Latched Shut-Down
Custom lengths, construction, cable types, ferrites, filters, and termination available upon request.
Approvals
Below follows a link to the latest regulatory certifications and marks for this specific product. National standards as well as certification schemes are constantly changing and so is the set of certification marks and symbols applicable to this product. Various standards, marks and symbols, and certificates are subject to change at any time without notice.
Additional standards or unique country certifications are available upon request. Please contact Globtek to request a quotation.
Logo
Description
Medical 4th Ed.
EN/IEC 60601-1-2, 4th Edition (Please visit EMC reports for further info)
No Logo Applicable
CB for IEC 62368-1:2014 (Second Edition)
Audio/Video, Information And Communication Technology Equipment - Part 1: Safety Requirements [UL 62368-1:2014 Ed.2] Audio/Video, Information And Communication Technology Equipment - Part 1: Safety Requirements [CSA C22.2#62368-1:2014 Ed.2]
Certification # TC RU AR46.B.69004 Custom Union of Russia, Belarus and Kazakhstan
Conforms to UL STD. 60950-1 Certified to CSA STD C22.2 NO.60950-1
Conforms to UL STD. 60950-1 Certified to CSA STD C22.2 NO.60950-1
Conforms to AAMI STD.ES60601-1,IEC 60601-1-11 Certified to CAN/CSA STD.C22.2 NO.60601-1
Conforms to AAMI STD.ES60601-1,IEC 60601-1-11 Certified to CAN/CSA STD.C22.2 NO.60601-1
UKCA Certification
Conforms to UL STD. 62368-1 Certified to CSA STD C22.2 NO.62368-1
Conforms to UL STD. 62368-1 Certified to CSA STD C22.2 NO.62368-1
CCC Altitude up to 5000 m GB17625.1-2012, GB4943.1-2011, GB/T9254-2008 for GT*43007
60601-1 3rd Operating Instructions
CHINA SJ/T 11364-2014, China RoHS Chart: http://www.globtek.com/pdf/F-GT-DJD-8.4.1-006%20China%20RoHS%20Declaration%205-20-22.pdf
WEEE: Complies with EU 2012/19/EU (http://ec.europa.eu/environment/waste/weee/index_en.htm) Mark is on the label or Molded in the case
Specifications of directive 2011/65/EU Annex VI (ROHS-2) with amendment 2015/863-EU (ROHS-3) http://www.ce-mark.com/Rohs%20final.pdf
Indoor Use Only - Mark is on the label or Molded in the case
No Logo Applicable
CB report IEC60601-1 2005 A1+C1+C2 2016-2-4 and or EN 60601-1:2006 3.1rd Edition 2xMOPP (6W max)
CE Mark: tested to comply with EN 60601-1-2:2015 Medical electrical equipment Part 1-2: - Mark is on the label or Molded in the case
CE Certification CE Mark: tested to comply with EN 55032.2012+AC.2013 EN 61000-3-2.2014 EN 61000-3-3.2013 EN 60601-1-2.2015 EN 55024.2010
FCC PART 15 CLASS B
LPS
Limited Power Source 60950
No Logo
CB Report EN60950-1
No Logo Applicable
CB to 60335-1 5th Edition (Safety of Household and Similar Electrical Appliances, Part 1: General Requirements) CB Report/ Certificate IEC 60335-1:2010 Up to 36 volts only
cETLus-Cert-4007497 ANSI/AAMI ES60601-1:2005/A1:2012 Issued: 2012/08/20 Medical electrical equipment ? Part 1: Amendment 1; CAN/CSAC22.2 No. 60601-1:14, Third Edition Issued: 2014/03/01 - Medical Electrical Equipment - Part 1
Efficiency: complies to section 301 of Energy Independence and Security Act (EISA) complies with Energy Star tier 2 (North America), ECP tier 2 (China), MEPS tier 2 (Australia), Code of Conduct (Europe)
Fuse 60335 T2.0A 250VAC Up to 36 volts
WDaE
Appliances can be used in warm damp equable climates