| GTM96060-AWWVV-FW |
|---|
 | GTM96060-AWWVV-FW, Medical/ICT/ITE/Household use Power Supply, Open Frame/Internal, Regulated Switchmode AC-DC Power Supply AC Adaptor, , Input Rating: 100-240V~, 50-60 Hz, PANEL MOUNT IEC 320/C8, cable UL1007, 18AWG, Length 60±10 mm, White & Black, S&T 9±1 mm, Output Rating: 6 Watts, Power rating with convection cooling (W) , 5-48V in 0.1V increments, Approvals: |
|---|
Information |
|---|
| Model Number | GTM96060-AWWVV-FW |
|---|
| Agency Documents | http://www.globtek.info/certs/GTM96060/ |
|---|
| CE EC-Declaration for Medical | Contact GlobTek for more information |
|---|
| CE EC-Declaration for Industrial/Commercial/ITE | Contact GlobTek for more information |
|---|
| CE EC-Declaration for Household | Contact GlobTek for more information |
|---|
| UKCA-Declaration for Medical | Contact GlobTek for more information |
|---|
| UKCA-Declaration for Industrial/Commercial/ITE | Contact GlobTek for more information |
|---|
| UKCA-Declaration for Household | Contact GlobTek for more information |
|---|
| Morocco SDoC Declaration | https://cs.globtek.info/Morocco_SDoC_Declaration?id=a0O3a00000NLXAvEAP |
|---|
| RoHS/RoHS3 Declaration | https://www.globtek.com/pdf/rohs_cert/a0O3a00000NLXAvEAP |
|---|
| Prop 65 Statement | https://www.globtek.com/r2/PH7CNf |
|---|
| REACH Declaration | https://www.globtek.com/r2/eM2co8 |
|---|
| Conflict Minerals Declaration | https://www.globtek.com/r2/vZY8R5 |
|---|
Model Parameters |
|---|
| Type | Open Frame/Internal |
|---|
| Technology | Regulated Switchmode AC-DC Power Supply AC Adaptor |
|---|
| Category | Medical/ICT/ITE/Household use Power Supply |
|---|
| Input Voltage Range (V) | 100-240V~, 50-60 Hz |
|---|
| Max Input Current (A) | 0.6 A |
|---|
| Max Output Power Rating (W) | 6 |
|---|
| Output Voltage Range (V) | 5-48 |
|---|
| Efficiency | N/A |
|---|
| Ingress Protection | N/A |
|---|
| Size (mm) | 84.50 x 41.50 x 17.0 |
|---|
| Enclosure |

|
|---|
| 3D File Download | http://www.globtek.com/dl/GTM43007A-LOW&HIGH-VERSION.igs |
|---|
Rating Table |
|---|
| Model Number (Final ordering #/Part No to be defined) | Voltage (V) | Current (A) | Power (W) | RFQ |
|---|
* (Final ordering #/Part No to be defined) |
Specifications |
|---|
Input| Input Voltage: | Specified: 90-264VAC, Nameplate: 100-240VAC 100% rated load current for 90-264VAC 85% rated load current for 85-264VAC 100% rated load current for 110-370VDC |
|---|
| Input Frequency: | Specified: 47-63Hz, Nameplate: 50-60Hz |
|---|
| No Load Input Power: | <75mW @ 230VAC |
|---|
| Inrush Current: | <30A @ 230VAC (cold start @ 25°C) |
|---|
| Efficiency: | DoE Energy Level VI and CoC Tier 2, for models 5V and above |
|---|
Output| Turn-on Delay: | 1 second max. @ 100VAC and full load |
|---|
| Output Regulation | ± 5% (measured at the output connector) |
|---|
| Line Regulation: | ± 1% (measured at the output connector @ full load) |
|---|
| Ripple: | 0.5% pk-pk or 50mV, whichever is greater (using a 47µF low-ESR cap + 0.1µF ceramic capacitor, measured @ 20MHz BW) (Note: < 0.2% or 25mV option available upon request) |
|---|
| Transient Response: | 5% deviation max. (with 25% load step), recovery to within 1ms typ. |
|---|
| Startup Overshoot: | <5% (full load) |
|---|
| Hold-up Time: | 8ms min. (100VAC and full load) |
|---|
| Power Indicator: | Green LED |
|---|
| Switching Frequency: | 65KHz typ. |
|---|
Protections| Input Protection: | 300Vac MOV transient suppressor, input line fusing |
|---|
| Over-Voltage Protection: | 110-130%, of nominal output voltage |
|---|
Current Limiting: (Standard CV Models): | Short circuit and overload protected, auto recovery Output current limit: 120% to 250% of rated output current (Upper end of current limit range is determined by normal output power rating, not derated output power level) |
|---|
Current Limiting: (Constant Current Models): | ± 10% of specified nominal output current rating Current regulated from Vout (nom.) to 0.25 * Vout (nom.) Average output current below 0.25 * Vout will be reduced, and unit will hiccup cycle |
|---|
| Over-Temperature Protection | On-chip temperature sensor (integrated in primary-side switching controller), shut down at Tj = ~140°C, restart at Tj = ~70°C |
|---|
Environmental| MTBF: | 1,500,000 hours @ 25°C ambient, full load (Telcordia SR-332, Issue 3) |
|---|
| Operating Temperature: | -10°C to 50°C (@ 6W load) See derating graph for output power capability outside of standard range. |
|---|
| Storage Temperature: | -30°C to 80°C |
|---|
| Humidity: | 0% to 95% relative humidity, non-condensing |
|---|
| Cooling: | Convection |
|---|
| RoHS: | Compliant with latest regulations |
|---|
Safety| Dielectric Withstand Voltage: | 4000VAC or 5656VDC from input to output |
|---|
| Touch Current: | <60µA |
|---|
| Earth Leakage Current | N/A, Class II input (No protective earth pin, therefore earth leakage is not measured) |
|---|
| Means of Protection: | 2 x MOPP |
|---|
| Primary-Secondary Bridging Capacitance: | Two 470pF IEC60384-14 certified Y1 capacitors in series |
|---|
EMC| Applicable Standards: | Medical: EN60601-1-2, 4th edition Emissions: EN55032, EN 55011, EN61000-6-3, EN61000-6-4, CISPR11, CISPR22 Immunity: EN55024, EN61000-6-1, EN61000-6-2 |
|---|
| Conducted Emissions: | Class B, FCC Part 15, Class B (with resistive load) |
|---|
| Radiated Emissions: | Class B, FCC Part 15, Class B (with resistive load) |
|---|
| Harmonic Current Voltage Distortion: | EN61000-3-2, Class A |
|---|
| Voltage Fluctuations/Flicker: | EN61000-3-3 |
|---|
| Electrostatic Discharge (ESD) Immunity: | EN61000-4-2, 10KV contact discharge, 18KV air discharge |
|---|
| Radiated RF Immunity: | EN61000-4-3, 10V/m 80-1000MHz, 3V/m 1-2.7GHz, 80% 1KHz AM |
|---|
| EFT/Burst Immunity: | EN61000-4-4, 4KV/100kHz. |
|---|
| Line Surge Immunity: | EN61000-4-5, 1.5KV differential, 4KV common-mode |
|---|
| Conducted RF Immunity: | EN61000-4-6, 3VRMS, 80% 1KHz AM |
|---|
| Power Frequency Magnetic Field Immunity: | EN61000-4-8, 3A/m |
|---|
| Voltage Dip Immunity: | EN61000-4-11 |
|---|
Enclosure| Housing: | Open frame PCB |
|---|
| Size: | 84.5*41.5*17.0 +/-1.0mm |
|---|
| Markings: | Label, pad printing, or laser engraving |
|---|
Special Options- Cost reduction, removal of LED
- Custom cordsets, various cordage types, and connector types
- Custom markings
- Reduced leakage current version, medical Type-CF leakage current compliance
- Tightened output voltage tolerance
- Reduced output ripple level
- Constant current battery charger characteristic
- Reduced output power rating
- High reliability PCB laminate with plated through-holes for IPC610 Class 2 Compliance
- Output voltage between 3.3V and 4.9V (without DoE EL6 and EU CoC Tier 2 compliance)
- Special housing colors and cordset colors
- Tamper proof, AC wall plug-in blade assembly. (Requires a special tool to remove the AC Wall Plug-in blade assembly.)
|
| Derating Curve |  |
|---|
| Qty (ea.)/Carton | 124 |
|---|
| Individual Box/Gift Box Size (mm) | 95*65*35 |
|---|
| Individual Box/Gift Box Color | 95*65*35 |
|---|
| Master Carton Size (mm) | 442 x 330 x 275 |
|---|
| Gross Weight (kg) | 15.2 |
|---|
| Label Width (mm) | 25.0 |
|---|
| Label Height (mm) | 17.0 |
|---|
Input Configuration |
|---|
| Description | PANEL MOUNT IEC 320/C8, cable UL1007, 18AWG, Length 60±10 mm, White & Black,
S&T 9±1 mm
|
|---|